AC 220V Standalone Natural Gas Alarm Coal gas Leaking detector NC NO relay Output

REF : DG220RN

$90.05

Volume discounts

5
$85.55
10
$81.05
20
$72.04
50
$67.54
100
$63.04
200
$58.54
500
$54.03
1000
$49.53
: 9 Items

Emplacement : G2

AC 220V Standalone Natural Gas Alarm Coal gas Leaking detector NC NO relay Output can network Fire sensor
 Firstly figure out the gas?s density in the air, then mount this detector near the gas source not far than 2.5m. (Note: The density of Coal Gas and Natural Gas is smaller than the air?s, so they are in the higher level. LPG?s density is smaller than the air?s, so it?s in a lower level)

Make sure the power supply and signal wires are connected to the detector correctly turn the power on. Then the device will start as follows:

1. Warm-up status. The red led indicator blinks once and the speaker sounds once.
2. Normal status. The green led indicator blinks once per minute for about 3 minutes.
3. Monitoring status. The green led indicator is on all the time.

To see if the detector is working properly, press the button S1 on the PCB. If the red led lamp is on and the speaker sounds, this means the detector is working properly.

When the density of Gas reaches 6%LEL, the led indicator will be red and blinks, the speaker will beep.(The alarm beeper frequency depends on the gas density, the higher the density is, the higher the frequency is)

When the emergency situation is settled, the detector can be reset to normal working status.

The red led indicator will blink and the speakers? last sounding if there?s malfunction happening to the detector, the inside delay will give out alarm signals. The detector can be set back to normal status when the malfunction is settled.

Testing and Maintenance
Testing methods: Keep filling gas into the hole for a least 5s when the detector is in monitoring status, if the flash and sound alarm is given out, it means the detector is working properly.(For example, you can use a gas light to do this test).

This product has high requirements for environmental conditions; please keep cleaning the detector timely (like removing the dust, oil, and moisture and so on). The sensitivity greatly depends on the cleanness of the detecting area.

Cautions:
Don?t mount this device in outdoor or moist places
Don?t mount this device near the places where the air circulation is very heavy, such as ventilation areas, fans, doors.
Don?t mount this device in the placed which are isolated from the gas source.
Make sure there isn?t too much chemical liquid used near this detector, like fixture, pesticide, ethanol and so on.

If malfunction happens, please check if the input and output lines is connected correctly. Warranty will be void if this product is opened by the users themselves.

DG220RN
9 Items

No customer reviews for the moment.

RETRAIT DANS NOTRE MAGASIN A TOULOUSE
RETRAIT DANS NOTRE MAGASIN A TOULOUSE
Our shop is open to collect your order from 9am to 1pm and from 2pm to 6pm from Monday to Friday
Free!
Colissimo Points de retrait
Colissimo Points de retrait
Delivery at post office, Pickup points & lockers
$7.17
Colissimo Domicile avec signature
Colissimo Domicile avec signature
Home delivery with proof of delivery
$9.55
Return
Free return within 14 days

You might also like

Produits dans la même catégorie

New Account Register

Already have an account?
Log in instead Or Reset password